| Model 2311AL Characteristics |
| | |
| Ethernet Interface | |
LAN Port Performance Data | 10/100baseT RJ-45 Female Packets, buffers, comm errors (MIBII) |
| | |
| LED Indicators | |
| | Power (green) Unit fail (red) Summary alarm (amber) Critical Alarm (red) Major alarm (red) Minor alarm (amber) Control asserted (green) LAN port activity (green and amber) |
| | |
| Craft Configuration Port | |
| 9 pin female D-Sub (DB9F) shielded | RS-232, 9,600 baud 8/N/1, no parity, no flow control Embedded Ethernet configuration program |
| | |
| Power | |
Input Power Range Power Consumption Power Connection | 18 to 56 VDC, floating 4 to 7 Watts Barrier Strip, three #6 screws (+, -, chassis ground) |
| | |
| Environmental | |
Operating Temperature Humidity Range Storage Temperature | 0 to +50° C 5% to 95%, Non-condensing -40 to +70° C |
| | |
| Physical Characteristics | |
Shelf Size Rack Mounting Shelf Weight | 1.75” H (1 RU), 19” W, 11” D Flush, 2” or 5 1/8” projection 5 pounds |
| | |
| Virtual Alarms | |
| Up to 16 virtual alarms can be created by Boolean logic combinations of external alarms |
| | |
| Alarm Inputs | |
50 pin female Centronics/Champ Programmable alarm delay before assertion | 32, Opto-isolated, 22 k to station battery Programmable as Alarm or Status |
| | |
| Control Outputs | |
50 pin female Centronics/Champ | 16, Form C relays 1 Alarm summary output, Form A relay Momentary or Latching Programmable NO or NC 1 amp max, DC 0.6 amp max, AC |
| | |
| Analog Voltages | |
optional, field upgradeable) 5 pin female D-Sub (DB25F) shielded | 16, ground referenced, single-ended inputs (use pairs for up to 8 differential inputs) can use both single-ended and differential) Each input has 5 plus or minus ranges (0 to 7.5, 15, 30, 60 or 120 VDC) Polarity and range set via software 52 k to ground, low pass filtered |
| | |